Home :: Sensors :: Temperature & Humidity :: RHT-Climate Temperature and Humidity Sensor 4 to 20mA/0-10VDC output, Modbus and LCD display

RHT-Climate Temperature and Humidity Sensor 4 to 20mA/0-10VDC output, Modbus and LCD display

RHT-Climate Temperature and Humidity Sensor 4 to 20mA/0-10VDC output, Modbus and LCD display

The RHT-Climate WM-485-LCD is a humidity and temperature transmitter that provides high precision and stability of measurements, over a wide operation range, it calculates in real time seven psychrometric properties, all variables will be available by current or voltage retransmission The RHT-Climate WM is intended for Wall Mount.

What is exciting about the RHT Climate

The RHT Climate is packed with features that are found in RHT transmitters and controllers that cost 2 or 3 times the price.

Measured Parameters - The RHT Climate can be configured to display and retransmit the temperature and relative humidity values , or any of its psychrometric properties, calculated in real time:

  • Dew Point Temperature
  • Wet Bulb Temperature
  • Absolute Humidity
  • Frost Point Temperature
  • Specific Enthalpy
  • Partial Vapor Pressure
  • Mixing Ratio

Accuracy – Temperature ±0,2 °C (0 °C to +60 °C) Humidity ±1,8 %RH @ +23 °C (0 %RH to 90 %RH)

Analog Outputs - Two 0-10 V or 4-20 mA outputs configurable by software or front panel keypad

Modbus RTU communications - For MONITORING, any supervision (SCADA) or laboratory software may be used that offers support for Modbus RTU communication over a serial RS485 communication port.

LCD Display - Using the keypad the operator can view temperature and humidity and all 7 psychrometric properties. The display will also show maximum and minum values of temperature, humidity and Dew point temperature.

Alarm Outputs – The RHT Climate has Two digital outputs and one embedded buzzer. The RHT Climate Transmitter allows for four options for its alarm outputs and for the buzzer:

  • - Normal operation;
  • - Activation for set time;
  • - Delay in activation;
  • - Intermittent activation

The hysteresis value for each alarm and buzzer is configurable. This allows the RHT-Climate to be used as a standalone temperature and humidity controller.

Configuration, Commissioning and Simulation – Versatile, the device allows configuration of parameters, simulation of temperature and humidity and generation of retransmission signal, useful features for commissioning on field in fast and easy way through USB with free PC software NXperience or directly by the keyboard.

Specifications:

  • Manufacturers Model: RHT-WM-USB-485-LCD
  • Temperature -
    • Temperature Range: -40,0 °C to 60,0 °C (WM models)
    • Accuracy Temperature: ±0,2 °C (0 °C to +60 °C)
    • Response time (1/e (63%)): < 5 seconds 25 °C (with air moving at 1 m/s)
  • Humidity -
    • Relative Humidity: 0.0 to 100.0 %RH (non-condensing)
    • Accuracy Relative Humidity: ±1,8 %RH @ +23 °C (0 %RH to 90 %RH)
    • Response time (1/e (63%)): < 4 seconds 25 °C (with air moving at 1 m/s)
  • Dew Point: -90,0 °C to 100,0 °C
  • Analog Outputs: Two 0-10 V or 4-20 mA outputs configurable by software or keyboard
  • Alarm Outputs: Channel N 30 V / 200 mA type output
  • Power supply: 2 Vdc to 30 Vdc; maximum consumption 70mA +/- 10% @ 24Vdc
  • Display: Wide backlight LCD with three variables of 4 ½ digits
  • Keys: 3 keys with tactile feedback for navigation and adjustment of parameters
  • Operating Temperature: -40 ° C to 60 ° C
  • Connections: Internal terminals through cable glands
  • Enclosure: IP65 Sensor: IP30, depending on the filter cap
  • Communication Interface: USB type Micro-B 2.0 and RS485 (both in Modbus RTU)
  • Programming: NXperience software for Windows through USB
  • Dimensions: 100.3 x 80.0 x 45.1 mm