PR103 MINI-PLC with ETHERNET/RS485 + 26I/O
PR103 is the first akYtec programmable relay with Ethernet on board. It is designed to control ventilation, heating, pump groups and other equipment. Ethernet interface allows to integrate the device into distributed systems, to realize remote control and management of equipment using akYtec Cloud service (Soon). Compact PLC PR103 has 2 RS-485 interfaces on board for data transmission to the upper level.
To expand its own inputs/outputs, the PRM expansion modules can be connected via the internal bus. Algorithm writing is performed by the user in FBD language with support of function blocks on ST in free programming environment ALP.
Algorithm loading and configuration is performed via microUSB, Ethernet or RS-485.
The PR103 is a mini-PLC with advanced communication capabilities thanks to its Ethernet port and two RS485 interfaces, as well as Modbus TCP and Modbus RTU/ASCII protocols. By communicating via RS485 interfaces at the field level, the small PLC PR103 can use the Ethernet port and Modbus TCP protocol to transmit data to the control level of the automation pyramid
The compact PLC PR103 modifications feature 10 digital inputs, up to 10 digital outputs, 6 analog inputs and a modification with 2 analog outputs and no analog outputs. In addition, 4 of the 10 digital inputs can be used as pulse counters that process signals from 100-kilohertz encoders. As for the analog inputs, they are configurable and can handle a wide range of RTD, NTC/PTC, and standard 4-20mA or 0-10V line signals. In addition, the built-in I/O can be directly expanded using two PRM series expansion modules.
Designed to be mounted on a DIN rail in a control cabinet, the PR103 can operate both in an unheated environment at temperatures down to -40°C and in a heated environment at temperatures up to +55°C.
The user program is written in the functional block diagram language with support for function blocks in the ST language in the free akYtec ALP software. The control algorithm is loaded into the device memory via micro USB cable, Ethernet or RS-485.
Features of PR103
Connected equipment:
- 10 digital inputs
- 4 fast digital inputs, up to 100 kHz.
- 6 analog inputs: PT1000, NTC/PTC, 4...20 mA/ 0...10 V, discrete mode, etc.
- Up to 10 digital outputs (e/m relays or transistor keys).
- Up to 2 universal analog outputs: 4...20 mA/0...10 V.
Communication capabilities:
Ethernet interface, Master/Slave mode:
- Direct access to akYtecCloud cloud service. (Soon).
- PC connection for program configuration and recording.
- Process visualization with operator panels and SCADA.
- Increase I/O with Mx210 modules
2 RS-485 interfaces, Master/Slave mode:
- Integration into SCADA systems.
- Process visualization via operator panels.
- Increase of I/O with Mx110 modules.
- Control of external devices: frequency converters, sensors, etc.
- Connection to PC for configuration and program recording.
Design features:
- Compact modular housing with a width of 7 modules
- Removable terminal blocks for easy installation.
- Quick battery replacement.
Operation:
- Power modifications: =24.
- Possibility of power supply from the on-board network =12 V.
- Increase I / O channels up to 32 pcs. with the help of modules PPM.
- Operation in unheated premises: -40...+55 °С.
- Configuration and program recording via USB, Ethernet and RS-485.
General | ||
---|---|---|
Power supply | 24 (9...30) V DC | |
Power consumption, max. | 8 W | |
Real Time Clock | Backup 5 years (CR2032) | |
Real Time Clock accuracy | ± 3 s/day | |
Extension modules | up to 2 PRMs |
Programming | ||
---|---|---|
Programming environment | akYtec ALP | |
Programming language | FBD | |
Programming interface | Mini-USB | |
Memory | ROM | 128 kB |
RAM | 32 kB | |
Retain memory | 1016 Byte |
Communication | ||
---|---|---|
Interfaces | 2x RS485 | |
Protocols | Modbus RTU / ASCII (Master / Slave) | |
Baud rate | 9.6...115.2 kBit/s |
Digital inputs | ||
---|---|---|
Quantity | 16 | |
Type | Switch contact | |
Logical states | 1 | 8.5...30 V DC (2...5 mA) |
0 | -3...+5 V DC (0...15 mA) | |
Galvanic isolation | none |
Universal inputs | |||||
---|---|---|---|---|---|
Quantity | 8 | ||||
Input signal | Analog / Digital | ||||
Galvanic isolation | none | ||||
Analog input | 4-20 mA, 0-10 V, 0-300 kOhm Pt1000, PTC, NTC (the complete list) | ||||
ADC resolution | 12 bit |
Digital outputs | |||||
---|---|---|---|---|---|
Quantity | 14 | ||||
Type | relay, NO | ||||
Galvanic isolation | individual | ||||
Switching capacity | AC | 5 A, 250 V (resistive load) | |||
DC | 3 A, 30 V | ||||
Minimum load current | 10 mA (at 5 V DC) |
Analog outputs | |||||
---|---|---|---|---|---|
Quantity | 2 | ||||
Analog outputs | 4-20 mA, 0-10 V | ||||
Permissible load | 12...30 V | ||||
DAC resolution | 12 bit | ||||
Galvanic isolation | individual |
Environment | ||
---|---|---|
Ambient temperature | -40...+55 °C | |
Storage temperature | -25...+55 °C | |
Humidity | up to 80 % (at +25 °C, non-condencing) | |
IP Code | IP20 |
Enclosure | ||
---|---|---|
Dimensions | 123 × 108 × 58 mm | |
Weight | approx. 250 g | |
Material | plastic |
Faulty Goods and Warranty
Where such goods have been supplied we undertake to repair or replace them as quickly as possible.Prior to returning faulty items, please contact us with a description of the fault as one of our engineers might be able to assist you by resolving the issue over the phone.
A Warranty form must be filled out and returned with any goods.
Our standard warranty period is 12 months from the date of purchase unless stated otherwise.
Other warranty periods:
Labjack Products: 5 Years
Atop Products: 3 Years
MeanWell Products: 3 Years
Terracom Products: 3 Years
Warranty is subject to us being satisfied that a defect was caused by defective workmanship or materials and was not caused by or was not substantially contributed to by other factors beyond our control including incorrect installation, alterations or modifications of the product not recommended by the manufacturer.
Returns Policy
If you are dissatisfied with our goods you may return them within 14 days of the dispatch date. Contact us for an authorisation and we will refund your purchase less shipping costs and restocking fees. All returned goods MUST be in AS NEW condition including ALL PACKAGING and DOCUMENTATION / MANUALS etc.
Please note:
- The product returned will attract a 20% restocking fee.
- The customer must pay the delivery costs.
- Non standard, custom made or a specially manufactured or imported products are not returnable.
- Semiconductors, books and software are not refundable
Full Terms and Conditions
By placing an order with Ocean Controls, you agree to be bound by our Terms and Conditions of Trade.
Name of the device | PR103-24 |
Programming | |
Programming environment | ALP |
Non-volatile memory capacity | 2040 bytes |
Network variable memory capacity (Slave mode) | 2040 bytes |
Number of network requests in Master mode | 192 |
Stack | Dynamic |
ROM memory | 224 KB |
RAM memory | 60 KB |
Programming and configuration interfaces | microUSB, Ethernet, RS-485 |
General information | |
Supply voltage range | 9...30 V (nominal = 24 V) |
Minimum program execution cycle time | 1 ms (depending on the program's complexity) |
Real-time clock | yes |
Expansion modules PRM | Yes, up to 2 |
Discrete inputs | |
Quantity | 6 pcs |
Connected sensors | Switching devices (button contacts, switches, relays, etc.), dry contact sensors Push-pull output sensors |
Nominal supply voltage | 24 V |
Galvanic isolation | In groups of 4 and 2 inputs |
Isolation voltage rating | 510 V |
Fast discrete inputs | |
Number of inputs | 4 |
Supported input types | Push-pull output sensors/Sensors with a push-pull output, |
Minimum pulse duration | 5 μs |
Maximum pulse frequency | 100 kHz |
Nominal supply voltage | 24 V |
Galvanic isolation | In groups of 4 inputs |
Isolation voltage rating | 510 V |
Analog inputs | |
Number of inputs | 6 |
Measured signal types | 4...20 mA, 0...10 V, Pt1000, NTC, PTC, 0...300 kOhm, etc. |
Maximum refresh rate of input values | 1 ms |
Discrete mode operation | Yes |
Galvanic isolation | none |
Discrete outputs | |
Number of outputs | Up to 10 |
Types of outputs | Relay (normally open) or transistor switch (NPN) |
Maximum permissible load | |
Relay output | 5 А at a maximum voltage of 250 V AC cos(φ) > 0,95; 3 А at a maximum voltage of 30 V DC |
Transistor [switch] output | 0,5 А at a maximum voltage of 40 V DC |
Galvanic isolation | |
Relay output | Individual |
Transistor [switch] output | None |
Isolation voltage rating | |
Relay output | 2300V |
Transistor [switch] output | None |
Analog outputs | |
Number of outputs | Up to 2 |
Types of output signals | Universal: 4...20 mА/0...10 V |
DAC resolution | 12 bits |
Galvanic isolation | Individual |
Isolation voltage rating | 510 V |
Communication features | |
Ethernet interface (1 pc) |
|
Communication protocol | Modbus TCP |
Operation mode | Master/Slave |
RS-485 interface (2 pcs) |
|
Communication protocol | Modbus RTU/ASCII |
Operation mode | Master/Slave |
Ambient temperature | -40...+55 °C |
Storage temperature | -25...+55 °C |
Humidity | up to 80% (at +25 °C, non-condensing) |
IP Code | IP20 |
Dimensions | 123 x 108 x 58 mm |
Weight | approx. 250 g |
Material | plastic |