Universal Input N1540 Process Indicator + RT 240 VAC (48x96mm)
Five digit universal process indicator accepts thermocouples, Pt100, 4 to 20 mA, 50 mV and 10 V signals. 4-20mA Analog Retransmission. 240 VAC Powered. Mini USB interface.
N1540 process meter was designed with advanced technology for highest performance and reliability in the most demanding applications. Based on an advanced and robust hardware platform, the N1540 can be fully programmed via its front keypad or via a USB interface. The unique USB interface makes the programming task a simple one step fool proof operation. It allows, for example, the set up of several instruments with the same programming parameters with extreme ease while saving precious time. The mini USB interface also provides an invaluable means for continuous monitoring of the measured process variable.
With a very short 34 mm depth enclosure, the N1540 can be easily installed in panels and enclosures where space is at a premium. Its 5-digit display allows the indication of high-resolution variables. It has 17mm high digits providing a clear view of the numbers and making it easier to read and diagnose even when operators are far from the indicator. The programmable 4-20mA analog retransmission is electrically isolated
Features:
- USB Interface for configuration and monitoring
- Factory configuration parameters retrieval
- Adjustable digital filter.
- Alarm Functions: LO, HI, differential, differential LO, differential HI, sensor break
- Alarm initial blocking, Alarm hysteresis
- Recorded maximum HI and minimum LO values can be retrieved via keypad
- Silicone rubber keypad
- Circuitry can be removed from housing without disconnecting wires.
- CE & UL certification
Power supply: 100 to 240 VAC/DC ±10%
Power consumption: 6 VA
Sensor input: J, K, N, R, T, S, B, E thermocouples, Pt100 RTD, 0 to 20 mA, 4 to 20 mA, 0 to 50 mV, 0 to 5 VDC and 0 to 10 VDC
Precision:
- JKTE T/C: 0.25% of span ±1ºC
- NRSB T/C: 0.25% of span ±3ºC
- Pt100: 0.2% of span
- mA, mV, V: 0.2% of span
Display range: -1999 to 9999
Displayed resolution: 12,000 levels
Internal resolution: 15 bits (32,767 levels)
Communication port: 2.0, CDC Class, Modbus RTU protocol
Output alarm 1: Relay SPST: 240 VAC/30VDC/1.5A
Output alarm 2: Relay SPST: 240 VAC/30VDC/1.5A
Operating temperature: 0 to 50 °C
Operating humidity: 80 %RH
Case: Polycarbonate (PC) UL94 V-2
Enclosure IP rating:
- Front panel: IP65, Polycarbonate UL94 V-2.
- Back panel: IP30, ABS+PC UL94 V-0.5 Digit LED display
Panel cutout: 93.0 x 45.5 mm
Weight: Approx.110 g
Dimension: 96 x 48 x 35 mm
Dispatch
In-stock orders are dispatched within 2 business days.
Shipping options
We deliver across Australia and internationally by any of the following methods:
- Australia Post Express
- Australia Post Parcel Post
- DHL
- FedEx (only international)
- Freight account. We'll email packaging dimensions when the shipment is ready to be book.
*Transit times vary depending on the shipping method and destination.
Store Pickup - Carrum Downs, Victoria, 3201
Order before 11am to collect after 2pm the same day. Mon–Fri, 9am–5pm, excludes public holidays.
RETURNS
How to return an item Contact us before sending anything back. Email info@oceancontrols.com.au or call +61 3 9708 2390. We'll confirm eligibility and guide you to the return process.
Return window 14 days from dispatch date.
Condition required Items must be unused and in original packaging, including all documentation and manuals.
Restocking fee A 20% restocking fee applies to all accepted returns. Return shipping costs are the customer's responsibility.
Non-returnable items
- Custom-made or specially imported products
- Software licences (some software have trial versions available)
- Items not in original, as-new condition
WARRANTY
How to make a warranty claim Before returning anything, please contact us. Our engineers can often resolve the issue remotely. If a return is required, our team will provide you with a warranty form to include with the goods.
What's covered Defects in materials and workmanship under normal use and correct installation.
What's not covered The warranty does not cover damage or failures caused by factors outside our control, including incorrect installation, unauthorised alterations or modifications, or any installation or use not recommended by the manufacturer.
Standard warranty All products carry a 12-month warranty from the date of purchase unless stated otherwise.
Extended warranty
- Labjack: 5 Years
- Atop: 5 Years
- MeanWell: 3 Years
- Teracom: 3 Years
- Novus: 3 Years