Power supply: 240 Vac/dc, 50/60 Hz
Maximum consumption: 3 VA
sampling rate: 5 per second
Analog output: 0-20 mA or 4-20 mA
Digital input: Dry contact or NPN open collector
Accepts inputs:
- Thermocouples type J, K, T, N, R, S
- Pt100 RTD
- Linear 4-20 mA, 0-50 mV, 0-5 Vdc.
Second analog input: 4 to 20 mA remote setpoint (Standard)
Accuracy:
- Thermocouples J, K, T: 0.25% of span ±1°C
- Thermocouples N, R, S: 0.25% of span ±3°C
- Pt100: 0.2% of span
- 4-20 mA, 0-50 mV, 0-5 Vdc: 0.2% of span
Internal resolution: 19500 levels
Ramp and Soak: 7 programs of up to 7 segments each. Can be linked to create longer programs of up to 49 segments.
Display: Double LED display (red for PV and green for SV )
Display resolution: 12000 levels (-1999 to 9999)
Control output:
- 2 relays SPDT (I/O1 and I/O2) - 3 A /240 Vac
- 2 relays SPST-NA (I/O3 and I/O4) - 1.5A / 250 Vac
- Logic pulse for SSR drive (I/O5): 10 Vmax / 20mA
Communication interface: RS-485 Modbus RTU and USB
EMC: EN 61326-1:1997 and EN 61326-1/A1:1998
Operating environment: 0 to 55 ºC
Operating humidity: 20 to 85 % RH
Protection:
Weight: 330 g
Panel cutout: 93 × 93 mm
Dimensions: 96 × 96 × 92 mm