Power supply: 10 to 30 VCC
Digital output: 1 NPN output (Alarm)
Function of digital output: Counts Pulses, Records Events or Starts Logger
Input signal: 1 digital input and 2 analog inputs
Type of analog signal:
- Thermocouples: J, K, T, N, E, R, S, B
- Pt100: 0-50 mV, 0-5 V, 0-10 V, 0-20 mA, 4-20 mA
Internal sensors: Battery voltage and external power supply
Display: 3 lines with 4½ digits
Resolution: 15 bits
Memory capability: 140000 records
Record interval: 10 s to 12 h
Variable record: Instantaneous or average
Acquisition trigger: Date/Hour, Start button, digital input or by software
Alarms: Up to 10 alarms Send by SMS
Phone Book: Up to 20 contacts
Internal buzzer: Yes
Communication interface: USB and Cellular 3G
Communication with SCADA or Cloud system: NOVUS Cloud and SCADA
Configuration software: NXperience forWindows
Operating temperature: -20 to 70 °C
Enclosure protection: IP40
Dimension: 120 x 100 x 40 mm
NXperience PC Software:
NXperience software is the main tool for configuration and data download of LogBox Connect. All parameters and features can be adjusted through LogBox USB interface, turning NXperience into a powerful tool for data analysis, graphical view, creation of mathematical formulas and report issuance. Nxperience can download data from several LogBoxes and transfer the data to the NOVUS Cloud. It is also possible to generate reports in .pdf and .xls formats.