CDR-MOD Room CO2 Sensor with Temperature with Modbus RS485

CDR-MOD Room CO2 Sensor with Temperature with Modbus RS485

SKU: SXS-350

CDR-MOD sensors are designed to detect carbon dioxide concentration and temperature in the room spaces and have Modbus RTU RS485 outputs

Produal (Syxthsense)
Buy more for less:
1-4items$265.58/ each 
5or more items$239.03/ eachsave10%
  • $265.58
Qty:  
Available for backorder

CDR-MOD Modbus CO2 sensors are designed to detect CO2 (carbon dioxide) concentration and temperature in the room spaces and have built-in Modbus RTU RS485 communication interface. The devices are addresses via bit switch or via the network. The Modbus CO2 sensor calibrates automatically its measurement using statistical analysis. The Modbus CO2 sensors have programmable linear 0..10V signals outputs. The CDR-MOD Modbus CO2 sensors have also a built-in digital and a resistive input (e.g. for external temperature measurement), and two additional digital outputs as standard.

The CDR-MOD Modbus CO2 sensors can be installed on wall surface or on a wall mounting box in dry indoor environment. The CDR Modbus sensors come with a number of additional options such as display, active setpoint, occupancy detection, lux level measurement, push button and additional digital and resistive inputs.

The CDR-MOD Modbus CO2 sensors can also operate as CO2, temperature, humidity or light level controllers modulating analogue outputs, or switching the digital output on based on the setpoints making them ideal for advanced control applications.

  • Modbus RTU RS485 Communication
  • Attractive Wall Mounted Room Enclosure (for UK/European/US mounting)
  • Adaptive CO2 Measurement Logic, Self-Calibrating
  • Large Range of Options to Suit Any Applications
  • Built-In Controller Functionality for CO2, Temperature and optional Humidity and Light Control
  • Can act as a Modbus Network IO-Module as well as Modbus CO2 Sensors and Modbus CO2 Controller
    • SKU
      SXS-350
    • Weight
      0.5 kg
    • Dimensions (L x W x H)
      22 x 15 x 7 cm
  • Power supply: 24Vac/dc -10%/+15%
  • Power consumption:  1VA (max)
  • Current Outputs: 2 x 4..20mA max 250 Ohms (0-10V optional)
  • Analogue Outputs: 3 x 0..10Vdc
  • Digital Outputs: 2 x 24Vac 2A Triac; requires 24Vac Power Supply (DO1 & DO2)
  • Resistive Input: 1 x NTC10/Resistive Input, 0..50kOhms (network value)
  • Digital Input: 1 x Digital Input, Volt-Free Contact, Impedance
  • Pulse Counting: Max 25Hz, Min Pulse Length 20mA (Volatile)
  • Procotol: Modbus RTU
  • Interface: RS485, maximum 63 devices
  • Addressing: 1..63 via a bit switch; 1..247 via tool / network
  • Carbon Dioxide (CO2) Detection:
    • Range: 0...5000ppm CO2 (Range Adjustable).
    • Accuracy: ± 50ppm + 3% of the reading @ 25°C
    • Warm Up Time:
    • Response time: 2 minutes
    • Signal Update Time: Every 2secs
    • Working Temp: 0~50degC (-10~50 optional).
  • Temperature:
    • Range 0..50°C (32..122°F)
    • Accuracy ±0.3°C
  • Dimensions: W86 x H120 x D29mm

Faulty Goods and Warranty

Where such goods have been supplied we undertake to repair or replace them as quickly as possible.Prior to returning faulty items, please contact us with a description of the fault as one of our engineers might be able to assist you by resolving the issue over the phone.
A Warranty form must be filled out and returned with any goods.

Our standard warranty period is 12 months from the date of purchase unless stated otherwise.

Other warranty periods:

Labjack Products: 5 Years
Atop Products: 3 Years
MeanWell Products: 3 Years
Terracom Products: 3 Years

Warranty is subject to us being satisfied that a defect was caused by defective workmanship or materials and was not caused by or was not substantially contributed to by other factors beyond our control including incorrect installation, alterations or modifications of the product not recommended by the manufacturer.

Returns Policy

If you are dissatisfied with our goods you may return them within 14 days of the dispatch date. Contact us for an authorisation and we will refund your purchase less shipping costs and restocking fees. All returned goods MUST be in AS NEW condition including ALL PACKAGING and DOCUMENTATION / MANUALS etc.

Please note:

  • The product returned will attract a 20% restocking fee.
  • The customer must pay the delivery costs.
  • Non standard, custom made or a specially manufactured or imported products are not returnable.
  • Semiconductors, books and software are not refundable

Full Terms and Conditions

By placing an order with Ocean Controls, you agree to be bound by our Terms and Conditions of Trade.

Related products

Customers who viewed this product also bought