Power supply: 12 to 30 VAC/VDC
Power consumption: 5 VA
Temperature resolution: 0.1°
Temperature measurement accuracy: ±0.5 to ±2 °C depending on temperature
Temperature repeatability: ±0.1°C
Temperature measurement range: -40 to 120 °C
Temperature response time: ≤30 seconds
Humidity resolution: 1%
Humidity measurement accuracy: ±3% from 20% to 80%
Humidity stability: ≤1 %RH / year
Humidity measurement range: 0 to 100 % RH
Humidity linearity error: ≤1 % RH
Humidity response time: 4 seconds (10 to 90 %)
Warm-up: 15 minutes
OUTPUT1 relay: SPDT, 1 HP 250 VAC / 1/3 HP 125 VAC (10 A Resistive)
OUTPUT2 relay: SPST, 3A / 250 VAC
Operating temperature: 0 to 40 °C
Storage temperature: -20 to 60 °C
Operating relative humidity: 20 to 85 % non condensing
Ingress protection (Front): IP65
Ingress protection (Rear): IP42
Suitable wiring: Up to 4.0 mm²
Panel cut-out: 70 x 29 mm
Weight: 100 g
Dimension: 74 x 32 x 75 mm