Fema C40-D Universal Input Process Indicator 18-265Vac/Vdc

Fema C40-D Universal Input Process Indicator 18-265Vac/Vdc

SKU: FMI-001

Four digit universal process indicator accepts thermocouples, RTD's, Thermistors, AC voltage and current (600VAC and 5AAC) , DC voltage and current (600VDC and 5ADC) and Frequency. 18 to 265 Vac/dc Powered. One analog output and one relay.

Fema
  • Manufacturer: Fema
Buy more for less:
1-4items$232.62/ each 
5-9items$209.36/ eachsave10%
10or more items$197.72/ eachsave15%
  • $232.62
Qty:  
In stock(4 items available)

Digital panel meter multisignal. Recommended for all type of industrial applications. Versatile and reliable, covers a wide range of analog signals with a single instrument. Variety of output and control options and accesories. Modular architecture.

Accepts AC voltages (from mVac up to 600Vac), AC currents (up to 5Aac), DC voltages (up to 600Vdc) and DC currents (up to 5Adc), frequency meter up to 100Hz for AC power lines, process signals (mA and Vdc), thermocouples (K, J, E, N, L, R, S, B, T and C), resistive temperature probes (Pt100, Pt500, Pt1000, Ni100, Ni200, Ni1000, PTC and NTC), resistances and potentiometers. Scalable reading with 4 digits up to 9999/-1999 with configurable decimal point.

Comes with options Analog Output and relay output

Features:

  • Accepts AC voltages (from mVac up to 600Vac) signals
  • Accepts AC currents (up to 5Aac) signals
  • Accepts DC voltages (up to 600Vdc) signals
  • Accepts DC currents (up to 5Adc) signals
  • Accepts frequency signals up to 100Hz for AC power lines
  • Accepts process signals (mA and Vdc) signals
  • Accepts thermocouples (K, J, E, N, L, R, S, B, T and C) signals
  • Accepts resistive temperature probes (Pt100, Pt500, Pt1000, Ni100, Ni200, Ni1000, PTC and NTC) signals
  • Accepts potentiometer signals
  • Adjustable digital filter.
  • Accepts front panel input of custom created non-linear curve with up to 30 points
  • Key panel protection through password to avoid tampering.
  • Alarms triggered above set point, below set point within range, out of range and sensor break detection.
  • Hold capability and peak and valley detection.
  • Tare function via front panel or via digital input.
  • Circuitry can be removed from housing without disconnecting wires.

Manufacturer Part No: Fema Electronica C40-D-U-M1-A2 

Power supply: 18 to 265 Vac/dc (isolated 1500 Veff @60 seconds)

Maximum power consumption: 2.5 VA

Digits: 4

Reading: 9999 / -1999

Decimal point:  configurable

Led color: red

Digit height: 14 mm

Accepted signal ranges:
    • AC voltages and AC currents ~600 Vac, ~200 Vac, ~20 Vac, ~2 Vac
    ~200 mVac, ~60 mVac, ~5 Aac, ~20 mAac
    (True RMS measure)
    (accepts phase-neutral and phase-phase measure)
    (frequency up to 150 Hz)
    • DC voltages and DC currents ±600 Vdc, ±200 Vdc, ±20 Vdc, ±2 Vdc
    ±200 mVdc, ±60 mVdc, ±5 Adc, ±20 mAdc
    • thermocouples K, J, E, N, L, R, S, B, T and C
    (automatic cold junction compensation)
    • resistive ‘Pt’ probes Pt100 with 2 and 3 wires, Pt500, Pt1000
    • resistive ‘Ni’ probes Ni100, Ni200, Ni1000
    • resistive NTC probes see table at page 3
    • resistive PTC probes families KTY-121, KTY-210 and KTY-220
    • process 4/20 mA, 0/10 Vdc
    (+15 Vdc excitation voltage configurable at terminal 5)
    • frequency up to 100 Hz (minimum 15 Hz). Vac and Aac ranges.
    • resistances ranges 0/5 K and 0/50 K
    • potentiometers with nominal values from 500 R up to 20 K

Output and control: 1 relay and 1 analog output 4/20 mA isolated

Thermal drift offset+span 150 ppm/ºC

Readings 3 readings / second

Refresh 3 refresh / second

Response time ≤ 300 mSec. (0 % to 99 % of signal)

Operating temperature: 0 to 55 °C 

Operating humidity: 20 to 95%RH Non-condensing

Weight: 150 g

Dimension: 96 x 48 x 91 mm

    • SKU
      FMI-001
    • Weight
      0.22 kg
    • Dimensions (L x W x H)
      13 x 10 x 7 cm

Dispatch

In-stock orders are dispatched within 2 business days.

Shipping options

We deliver across Australia and internationally by any of the following methods: 

  • Australia Post Express
  • Australia Post Parcel Post
  • DHL
  • FedEx (only international)
  • Freight account. We'll email packaging dimensions when the shipment is ready to be book.

*Transit times vary depending on the shipping method and destination.

Store Pickup - Carrum Downs, Victoria, 3201

Order before 11am to collect after 2pm the same day. Mon–Fri, 9am–5pm, excludes public holidays. 

RETURNS

How to return an item Contact us before sending anything back. Email info@oceancontrols.com.au or call +61 3 9708 2390. We'll confirm eligibility and guide you to the return process.

Return window 14 days from dispatch date.

Condition required Items must be unused and in original packaging, including all documentation and manuals.

Restocking fee A 20% restocking fee applies to all accepted returns. Return shipping costs are the customer's responsibility.

Non-returnable items

  • Custom-made or specially imported products
  • Software licences (some software have trial versions available)
  • Items not in original, as-new condition


WARRANTY

How to make a warranty claim Before returning anything, please contact us. Our engineers can often resolve the issue remotely. If a return is required, our team will provide you with a warranty form to include with the goods. 

What's covered Defects in materials and workmanship under normal use and correct installation.

What's not covered The warranty does not cover damage or failures caused by factors outside our control, including incorrect installation, unauthorised alterations or modifications, or any installation or use not recommended by the manufacturer.

Standard warranty All products carry a 12-month warranty from the date of purchase unless stated otherwise.

Extended warranty 

  • Labjack: 5 Years
  • Atop: 5 Years
  • MeanWell: 3 Years
  • Teracom: 3 Years
  • Novus: 3 Years


Related products