Power supply: 12 to 30 Vdc or 3.6 V Lithium Battery
Maximum consumption: 70 mA
Interval between updates: Configurable between 15 seconds and 10 minutes (600 s)
Estimated battery life: Typical 2 years - 10 minutes update interval at 25°C
Temperature:
- Measurement range: -40 °C to 100 °C / -40 °F to 212 °F
- Measurement accuracy: ±2 °C / ±3.6 °F
- Measurement resolution: 0.1 °C / 0.1 °F
Humidity:
- Measurement range: 0 to 100% RH
- Measurement accuracy: ±3% (20-80 °C / 68-176 °F) and ±5% (0-100 °C / 32-212 °F)
- Measurement resolution: 0.1% (12 bits - 4095 levels)
Response time:
- Temperature: 30 Second (air speed 1 m/s)
- Humidity: 8 Second (air speed 1 m/s)
Display: LCD with 2 indicators
Communication interface: NOVUS air (IEEE 802.15.4)
USB configuration: Internal micro-B Type
Certifications:
- CE
- ANATEL (0172-13-7089)
- FCC
EMC: EN61326-1:2006 CISPR11/EN55011, EN61000-4-2, EN61000-4-3, EN61000-4-4, EN61000-4-6, EN61000-4-8
Operating temperature: -10°C to 70°C (14 °F to 158 °F)
Operating humidity: 0 to 95% RH
Probe size: 39 mm
Antenna size: 105 mm
Dimension: 70 x 60 x 35 mm
Software:
The latest DigiConfig Software can be downloaded from the Novus Automation website at: http://www.novusautomation.com/products/527250