TCW241 Ethernet Digital IO, Voltage, Temperature, Humidity Alarm and Control
The TCW241 is an Ethernet control unit with 4 digital inputs, 4 relay outputs, 4 analogue inputs and a 1-Wire interface for up to 8 x 1-Wire sensors.
TCW241 is an Ethernet I/O module. It provides four digital inputs, four relay outputs and four analog inputs. Its 1-Wire interface supports up to eight sensors like temperature, humidity, CO2, AC/DC current, 4/20mA etc.
The Ethernet I/O module has real-time clock (RTC) with time server synchronization (NTP) for advanced relay scheduler. It can be used for one-time or repetitive (weekly) tasks to turn on/off relays at previous set times.
TCW241 can initiate a connection (HTTP Post) to remote dedicated servers. The payload of this post is XML or JSON file, with current values of monitored parameters. HTTP post can be send periodicaly or on previous set alarm conditions. The relays of Ethernet I/O module can be activated either remotely or locally. So called remote activation includes friendly WEB interface or M2M protocols – MODBUS TCP/IP, SNMP and HTTP API. The local activation is possible from scheduler, status of single parameter or by custom made functions. They can include up to four parameters.
- 4 digital inputs with "dry contact" and "logic level" modes
- 4 analogue inputs with 0 to 60VDC range, 0.01V resolution
- 4 relays with NO and NC contacts
- Relay rating: 30VAC, 24VDC, 3A
- 1-Wire support for up to 8 1-wire temperature/humidity sensors
- SNMP traps on alarm
- e-mail on alarm
- XML and HTTP API commands
- Modbus TCP/IP support
- Android and Apple iOS Apps
- NTP protocol support
- Push mode for client-server systems
- Real time clock for scheduled time/date control
- Power: 8-32VDC at 300mA
- Dimensions: 145mm x 90mm x 40mm
- Operating temperature: -20°C to +70°C
- DIN Rail mount enclosure
TC Monitor is easy to use Windows application for monitoring and control of TCW products. TC Monitor can collect and display data from controllers installed in different locations (sites). The collected data is stored in SQL database and can be displayed or exported in MS Excel format for further analysis. TC Monitor has a simple web interface, which enables easy and fast configuration. Monitored parameters can be 1-wire sensors, digital and analog inputs and relay outputs. The free version of TC Monitor provides 10 credits, this means up to 10 different parameters can be monitored and logged.
- Supply voltage: 10 - 32 VDC
- Maximum current ( with all relays ON): 350@12VDC mA
- Weight: 230 g
- Dimensions: 145 x 90 x 40 °C
- Operating temperature: -20 to +55 °C
- Maximum humidity: 70 %RH
- Minimum high level input voltage for digital inputs: +2.5 VDC
- Maximum low level input voltage for digital inputs: +0.8 VDC
- Maximum input voltage for digital inputs: +5.5 VDC
- Supply voltage for 1-Wire bus (VDD): 5.0 ± 0.3 VDC
- Maximum output current for 1-Wire bus (VDD): 0.2 A
- Analog inputs range: 0 to 60 VDC
- Analog inputs resolution: 0.01 VDC
- Analog inputs accuracy: ± 1%
- Maximum switchable current: 3 A
- Maximum switchable voltage: 30/24 VAC/VDC
Faulty Goods and Warranty
Where such goods have been supplied we undertake to repair or replace them as quickly as possible.Prior to returning faulty items, please contact us with a description of the fault as one of our engineers might be able to assist you by resolving the issue over the phone.
A Warranty form must be filled out and returned with any goods.
Our standard warranty period is 12 months from the date of purchase unless stated otherwise.
Other warranty periods:
Labjack Products: 5 Years
Atop Products: 3 Years
MeanWell Products: 3 Years
Terracom Products: 3 Years
Warranty is subject to us being satisfied that a defect was caused by defective workmanship or materials and was not caused by or was not substantially contributed to by other factors beyond our control including incorrect installation, alterations or modifications of the product not recommended by the manufacturer.
Returns Policy
If you are dissatisfied with our goods you may return them within 14 days of the dispatch date. Contact us for an authorisation and we will refund your purchase less shipping costs and restocking fees. All returned goods MUST be in AS NEW condition including ALL PACKAGING and DOCUMENTATION / MANUALS etc.
Please note:
- The product returned will attract a 20% restocking fee.
- The customer must pay the delivery costs.
- Non standard, custom made or a specially manufactured or imported products are not returnable.
- Semiconductors, books and software are not refundable
Full Terms and Conditions
By placing an order with Ocean Controls, you agree to be bound by our Terms and Conditions of Trade.