Universal Input N1040i-RA Indicator 240VAC Power 1 Relay, Analog Retransmission
N1040i-RA Process indicator accepts thermocouple, Pt100, and linear current or voltage signals. Display range is configurable. 1 alarm relay output and 4 to 20 mA analog retransmission. 240 VAC powered.
The Universal Indicator N1040i combines, in one compact and convenient 1/16 DIN enclosure, a high precision microprocessor based analog circuit with a very simple configuration interface to monitor a wide range of analog variables.
This low cost, tough and versatile indicator is compatible with most common thermocouple types, Pt100 RTD sensor and linear 4 to 20 mA and mV sensors.
With a intuitive interface to program range and decimal point through the keypad, the N1040i allows inexperienced instrumentation operators easy installation and start up for most processes.
The N1040i-RA Process indicator features 1 alarm relay, 4 to 20 mA analog retransmission and is 240 VAC Powered
Features:
- Input adjustable offset allows small indication corrections
- Configurable initial alarm blocking function doesn't "arm" alarm until the process has reached normal operating conditions
- Flash alarm function alerts operator to condition while in alarm state
- Sensor failure detection
- Password for meter protection
- Factory calibration parameters recovery
- Certifications: CE, UL
Power supply: 100 to 240 VAC ±10%, 50/60 Hz
Maximum power consumption: 6 VA
Sensor input:
- J, K, T, E, N, R, S, and B
- Pt100
- 0 to 50 mV
- 4 to 20 mA
- 0 to 5 VDC
- 0 to 10 VDC
Output: 2
- Alarm output capable of minimum, maximum, differential, minimum differential, maximum differential and sensor break alarm conditions
- Retransmission of PV
Accuracy:
- Thermocouples J, K, T, E: 0.25% of the span or 1 ºC
- Thermocouples N, R, S, B: 0.25% of the span or 3 ºC
- Pt100: 0.2% of the span
- 4 to 20 mA, 0 to 50 mV, 0 to 5 V, 0 to 10 V: 0.2% of the span
Display: Five digit 13 mm ultra bright LED display
Internal Resolution: 32767 levels (15 bits)
Display Resolution: 12000 levels (i.e -1999 to 9999)
Input reading rate: Up 55 per second
Programmable scaling: From -1999 to +9999 and adjustable digital filter
Operating temperature: 0 to 55 °C
Operating humidity: 80% at 30°C (For temperatures above 30°C, reduce 3% per °C)
Front panel: IP65, Polycarbonate UL94 V-2
Back panel: IP30, ABS+PC UL94 V-0.5 Digit LED display
Weight: 265 g
Dimension: 96 x 48 x 92 mm
Faulty Goods and Warranty
Where such goods have been supplied we undertake to repair or replace them as quickly as possible.Prior to returning faulty items, please contact us with a description of the fault as one of our engineers might be able to assist you by resolving the issue over the phone.
A Warranty form must be filled out and returned with any goods.
Our standard warranty period is 12 months from the date of purchase unless stated otherwise.
Other warranty periods:
Labjack Products: 5 Years
Atop Products: 3 Years
MeanWell Products: 3 Years
Terracom Products: 3 Years
Warranty is subject to us being satisfied that a defect was caused by defective workmanship or materials and was not caused by or was not substantially contributed to by other factors beyond our control including incorrect installation, alterations or modifications of the product not recommended by the manufacturer.
Returns Policy
If you are dissatisfied with our goods you may return them within 14 days of the dispatch date. Contact us for an authorisation and we will refund your purchase less shipping costs and restocking fees. All returned goods MUST be in AS NEW condition including ALL PACKAGING and DOCUMENTATION / MANUALS etc.
Please note:
- The product returned will attract a 20% restocking fee.
- The customer must pay the delivery costs.
- Non standard, custom made or a specially manufactured or imported products are not returnable.
- Semiconductors, books and software are not refundable
Full Terms and Conditions
By placing an order with Ocean Controls, you agree to be bound by our Terms and Conditions of Trade.